Friday 10 February 2012

Voltage

Under / Over Voltage
   

Over Voltage is an increase in effective voltage to more than 110% for longer than one minute. Under Voltage is a decrease in effective voltage to less than 90% for longer than one minute. Take care with this definition because it tends to change from vendor to vendor.


Transient Voltages / Spikes / Surges
   

Refers to short duration (less than 1 cycle) events. Low frequency transients are often called "capacitor switching transients". High frequency transients are often called impulses, spikes, or surges. They can be caused when a discharged power-factor-correction capacitor is switched on across the line.

High frequency transients are caused by lightning, and by inductive loads turning off. Typical rise times are on the order of a microsecond; typical decay times are on the order of a tens to hundreds of microseconds. Often, the decay will be an exponential damped ringing waveform, with a frequency of approximately 100 kHz.

Extremely fast transients, or EFT's, have rise and fall times in the nanosecond region. They are caused by arcing faults, such as bad brushes in motors, and are rapidly damped out by even a few meters of distribution wiring. Standard line filters, included on almost all electronic equipment, remove EFT's.



Power Meter Solutions Using FieldServer











Convert Power Meters to BACnet.

    Includes configuration for a single meter
    Includes Free CAS BACnet Explorer license.
    Offer applies for certain meters only. Small extra fees apply for configurations which connect to multiple meters. Contact us for more info..







Real Power & Reactive Power

No comments:

Post a Comment