SNVT Name: SNVT_btu_kilo
SNVT Index: 5
- Number of Data Array elements required i.e the Data length for SNVT_btu_kilo when specifying a Data Array name under a Map Descriptor is 1.
- The value range allowed for this SNVT type is 0 .. 65,535 and the values outside this range will not be processed in a read or write on SNVT_btu_kilo's value data item.
- The suggested data array format for SNVT_btu_kilo is Uint16, Float format.
- Invalid value will always be "Not applicable" (N/A).
- It contains only one data item named Thermal Energy which is measured in Kilo-British Thermal Units.